-
What
are harmonics?
-
What happens to
the fundamental frequency’s sinusoidal waveform when harmonics are present?
-
What causes
harmonic currents?
-
What causes
harmonic voltages?
-
Is there really a
harmonics problem?
-
What causes the
harmonic problems?
-
How big is the
harmonics problem?
-
How have engineers
allowed for harmonics in their system designs?
-
Is there a
solution to the problems caused by harmonics?
-
Who are the
‘stakeholders’ if the harmonic problems are not solved?
-
What is IEEE Std
519-1992?
-
What will happen
to my loads if I allow the electrical system to operate outside IEEE Std
519-1992 guidelines?
-
What will happen
to my electrical system if I allow it to operate outside IEEE Std 519-1992
guidelines?
-
Will harmonic
currents affect my power costs?
-
Can I purchase a
harmonic mitigating transformer that will solve all my harmonic problems?
-
Why should I
consider a harmonic filter(s)?
-
Where is the best
place to remove harmonic currents?
-
What will happen
if I install a 180Hz zero-sequence current high impedance blocking filter at
the ‘load-side’ of a distribution transformer?
-
What does
K-Rating really mean?
-
Should I apply a
transformer that is only capable of supporting a sub-system that supplies
not more than 50% nonlinear electronic loads?
-
Does the
Department of Energy’s Oak Ridge National Laboratory validate and endorse
the performance of harmonic mitigating transformers?
-
Are manufacturer’s
published transformer efficiency claims, under nonlinear load conditions,
legitimate?
-
Why should I
specify PQI products?
1. What are harmonics?
Harmonic
currents and voltages are integer multiples of the system’s fundamental
frequency. For example, with a fundamental frequency of 60Hz, the 3rd harmonic
frequency is 180Hz (3 x 60Hz).
2. What happens to the fundamental
frequency’s sinusoidal waveform when harmonics are present?
The fundamental
frequency’s sinusoidal waveform, which is always predominant, becomes distorted
by the addition of harmonic sinusoidal waveforms. The measure of distortion is
given as Percent Total Harmonic Distortion of the Fundamental Waveform (%THDv
[voltage] & %THDI [current]).
3. What causes harmonic currents?
Nonlinear loads
are the source of harmonic currents. That is, the load’s current waveform is
non-sinusoidal. As a result, the distorted current waveform is rich in
sinusoidal harmonic current waveforms.
Nonlinear loads
include electronic devices such as rectifiers, current controllers, AC and DC
drives, cyclo-converters and devices with switch-mode power supplies such as
computers, monitors, telephone systems, printers, scanners, and electronic
lighting ballasts.
4. What causes harmonic voltages?
The electrical distribution system’s harmonic impedances cause the
load-generated harmonic currents to produce harmonic voltages (EH = IH
x ZH). Transformers, and feeder and branch circuit impedances will
cause maximum voltage distortion at the nonlinear loads.
5. Is there really a harmonics problem?
Yes, there is a
problem. In fact, there are so many significant harmonics problems that
hundreds, if not thousands, of theses, papers, articles and case studies have
been published on this subject. To define and limit harmonic problems, IEEE has
published a standard entitled - ‘Recommended Practices and Requirements for
Harmonic Control in Electrical Power Systems’ (ANSI/IEEE Std 519-1992).
6. What causes harmonic problems?
All electronic
loads generate positive- and negative-sequence harmonic currents. Single-phase
electronic loads, connected phase-neutral in a three-phase, four-wire
distribution system, also generate zero-sequence harmonic currents. Three-phase
motor drives and single-phase lighting loads often account for a significant
portion of a system’s 480V loads. Single-phase electronic office and data
processing equipment typically accounts for more than 95% of a 120/208V power
panel’s loads. At these levels, 100% Total Harmonic Distortion of Current is
common.

7. How big are the harmonics problems?
In the early
1980s, the proliferation of personal computers and conversion to electronic
lighting ballasts produced harmonic problems in commercial office buildings.
Facility managers and designers soon discovered that single-phase electronic
loads caused distribution transformers to overheat and ‘shared’ neutral
conductors to become overloaded.
Today, more
than 95% of all 120/208V power panel loads, in modern office and data center
environments, are electronic. Electronic motor drives are now routinely applied
to ventilation fans and elevators at the 480V level.
8. How have some engineers dealt with
harmonics in their system designs?
To improve
system performance and provide the best possible environment for nonlinear
loads, a designer’s options have been limited to over-sizing distribution
transformers and ‘shared’ neutral conductors.
As an
alternative, branch circuits have been configured with a separate neutral
conductor for each phase conductor. In either case, branch circuits have been
underutilized and limited in their length as a means of reducing voltage
distortion and neutral-ground voltage (common mode noise) at the loads.
As an
alternative to over-sizing conventional distribution transformers, many
designers have specified K-Rated transformers. Unfortunately, a K-Rated
transformer’s higher harmonic impedances cause an increase in voltage
distortion.
9. Is there a solution to the problems
caused by harmonics?
Yes, there is a
solution. The reduction of harmonic currents will solve all of
the harmonic-related problems.
The PQI Solution™,
an engineered system solution, includes a Statement of Design Objectives, a
comprehensive System Study, a detailed Mitigation Proposal, and a System
Performance Guarantee.
10. Who are the ‘stakeholders’ and
what are their problems if the harmonic problems are not solved?
The
‘stakeholders’ include the electrical distribution system designer, the facility
owner, the tenant(s) and, ultimately, the tenant’s clients or customers. Their
potential problems include:
The
Designer
-
Harmonics Exceed
IEEE Recommendations & Requirements,
-
Harmonics Exceed CBEMA / EPRI Recommendations,
-
Power
System and Loads are Incompatible,
-
Project Exceeds
Budgetary Goals and
-
Loss of
Client Confidence.
The
Facility Owner
-
High
Capital Costs,
-
Increased Fire & Safety Risks,
-
Premature Apparatus Failures and
-
Significant Tenant Dissatisfaction.
The Tenant
-
Higher
Power Cost,
-
Premature Office Equipment Failures,
-
Data
Corruption or Loss,
-
Computer and System Lock-Ups,
-
Loss of
Productivity,
-
Reduced
Quality Assurance,
-
Loss of
Customer Confidence and
-
Loss of
Revenue.
The
Client/Customer
-
Higher
cost for products and/or services,
-
Reduced
product and/or service quality,
-
Loss of
Customer Confidence and
-
Loss of
Revenue.

11. What is IEEE Std 519?
ANSI/IEEE Std
519-1992 – Recommended Practices and Requirements for Harmonic Control in
Electrical Power Systems is the recognized power quality standard in North
America. From this standard we wish to provide the following sections:
Section 10.3
– Limits on Commutation Notching, states that - ‘The notch depth, the total
harmonic distortion factor (THD), and the notch area of the line-to-line voltage
at PCC should be limited as shown in Table 10.2.’
|
Table 10.2
Low-Voltage System Classification and Distortion Limits |
|
|
Special
Applications [1] |
General Systems |
DedicatedSystems
[2] |
|
Notch Depth
THD (Voltage)
Notch Area (AN)[3] |
10%
20%
50% |
3%
5%
10% |
16 400
22 800
36 500 |
Note: The value
AN, for other than 480V systems, should be multiplied by V/480.
[1] Special
applications include hospital and airports.
[2] A dedicated system is exclusively dedicated to the converter load.
[3] In volt-microseconds at rated voltage and current.
Section 11.5
– Voltage Distortion Limits, states that - ‘the limits listed in Table 11.1
should be used as system design values for the “worst case” for normal operation
(conditions lasting longer than one hour). For shorter periods, during start-ups
or unusual conditions, the limits may be exceeded by 50%.
|
Table 11.1
Voltage Distortion Limits |
|
Bus Voltage at PCC |
Individual Voltage
Distortion (%) |
Total Voltage
Distortion THD (%) |
|
69kV and below
69.001kV through 161kV
161.001kV and above |
3.0
1.5
1.0 |
5.0 [1]
2.5
1.5 |
[1] From
Section 10.3 above, a THDv
of 3% is required for hospitals and airports.
It is important
to understand that THDv
limits apply at the point of load connection. THDv
levels at the loads may be several times higher than those at the distribution
transformer’s secondary terminals. It is, after all, the loads that require
reasonable levels of voltage distortion.
12. What will happen to my loads if I
allow the electrical system to operate outside IEEE Std 519-1992 guidelines?
Electronic
equipment is susceptible to misoperation caused by harmonic distortion. Data in
computer ‘networks’ may be corrupted. Harmonic currents may also contaminate
audio and video signals in interconnecting shielded cables.
Conventional
linear loads can also be affected. For example, motors may act as an unintended
harmonic shunt. This will result in loss of torque, overheating and premature
failure.
Sections 6.2,
6.6 and 6.9 of the standard detail the probable outcomes if harmonic currents
and voltages are not controlled.
13. What will happen to my electrical
system if I allow it to operate outside IEEE Std 519-1996 guidelines?
Harmonic
currents, generated by single and three-phase nonlinear electronic loads, will
cause additional ‘penalty’ losses throughout the electrical distribution system.
These losses result in apparatus overheating and premature apparatus failure.
Section 6.0 of the standard details the probable outcomes if harmonic currents
and voltages are not controlled.

14. Will harmonic currents affect my
power costs?
Harmonic
currents, generated by single and three-phase nonlinear electronic loads, will
cause significant ‘penalty’ losses throughout the electrical distribution
system. For example, distribution transformers, when supporting 100% THDI
nonlinear electronic office loads, will produce approximately 3.25 times higher
losses than when supporting linear loads. ‘Penalty’ losses, produced by the
other elements of the sub-system, will typically equal and often substantially
exceed the transformer’s ‘penalty’ losses.
‘Penalty’
losses result in apparatus overheating, higher air conditioning costs and higher
power costs. A reduction in ‘penalty’ losses will produce a very attractive
annual saving. An approximate saving may be calculated as follows:
|
Annual Savings = |
(Total kW Savings
$/kWh hrs/day days/year) +
(Total kW Savings $/kW Demand Charge/month 12 months) +
(Total PF Penalty Savings) |
15. Can I purchase a harmonic
mitigating transformer that will solve all my harmonic problems?
No! Since the
vast majority of harmonic mitigating distribution transformers are used to
supply switch-mode power supply loads, it is likely that these transformers will
have secondary windings with ultra-low zero-sequence impedance. This
characteristic normally allows for the cancellation of zero-sequence fluxes by
the secondary windings, a reduced core cross-section, avoidance of zero-sequence
current in the primary ‘delta’ connected windings, and relatively low losses and
high efficiency. The transformer also provides a reduction in THDv at
its secondary terminals. These are the benefits.
However, in
reducing the distribution transformer’s zero-sequence harmonic impedances (Z0),
load-generated zero-sequence harmonic currents will increase. zero-sequence
harmonic currents are normally limited by the conventional transformers
relatively high zero-sequence impedances. For example, a conventional or K-Rated
transformer may have a Z0 of 0.1Ω.
By contrast, a harmonic mitigating transformer, with ultra-low zero-sequence
impedance, may have a Z0 of less than 0.005Ω,
20 times less than a conventional or K-Rated Transformer.
In this
scenario, zero-sequence harmonic currents will increase in the phase and neutral
conductors. This, in turn, will cause even higher ‘penalty’ losses in the
120/208V feeder and branch circuits and, most importantly, higher neutral to
ground (CMN) voltages at the loads.
High CMN is
normally the most significant ‘power quality’ problem since it causes data
corruption in computer ‘networks’. In addition, high voltage distortion (THDv)
will cause switch-mode power supplies to overheat and reduce their life
expectancy.
All issues
considered, and as a ‘rule-of-thumb’, it is often inappropriate to apply
ultra-low zero-sequence harmonic mitigating transformers in ratings above 75kVA.
With higher ratings, circuit lengths tend to be longer and, consequently, THDv
and CMN levels will be unacceptable.
Manufacturers
who recommend the application of these types of harmonic mitigating
transformers, even with improved efficiencies, while ignoring the critical
‘power quality’ issues, do a disservice to their customers, and the utilities
that may subsidize the application of their products.
An engineered
system solution may provide the only acceptable alternatives if a sub-system’s
capacity exceeds 75kVA. An engineered solution will always provide the best
power cost reduction.
The PQI Solution™, an engineered system solution, is available
to designers on a free-of-charge basis. Total system efficiency and ‘power
quality’ outcomes are guaranteed.
16. Should I consider harmonic
filters?
With reference
to the preceding question (15), the only alternative, in solving all the
harmonic problems, may be the application of zero-sequence harmonic filters,
particularly if the transformer’s rating is higher than 75kVA.
17. Where is the best place to remove
harmonic currents?
The best place
to remove harmonic currents is often at the nonlinear loads that generate
harmonic currents or, alternately, at the sub-panels that supply the branch
circuits. The object is to reduce harmonic current at a point that is
as-close-as-possible to the harmonic generating nonlinear loads. The reduction
of harmonic current will result in the reduction of ‘penalty’ losses.
I0Filter™ or
Mini-Z™
zero-sequence harmonic filters may be used for this purpose.
18. What will happen if I install a
180Hz zero-sequence current high impedance blocking filter at the ‘load-side’ of
a distribution transformer?
In most
applications, this type of current blocking filter will substantially increase
voltage distortion (THDv) at the loads.
Several
independent NETA companies reported THDv values in excess of 20%. One
UPS/PDU manufacturer, which was obliged to install this type of filter at the
output of its PDU, reported a 15% THDv increase after its
installation. In this instance, a system that was marginal with a 4% THDv,
before the installation of the filter, rose to 19% after the installation.
A designer or
facility manager, who specifies this type of filter, assumes that the
load-generated zero-sequence harmonic currents have no alternative parallel
zero-sequence path than the secondary windings of the distribution transformer. This
assumption has caused serious apparatus and system failures.
In addition,
some sensitive electronic loads and distribution system devices will reject the
highly distorted voltage as being unsuitable. For example, small single-phase
UPSs may transfer their loads to the battery backup, until they are discharged,
then remain unavailable when a system ‘reclosure’ or ‘outage’ occurs.
One independent
testing company has also reported an increase in transformer core losses and
temperatures after a blocking filter installation. This test was conducted as part of a
general assessment of the filter’s characteristics and benefits. In this case,
the purpose in adding the filter was to reduce the distribution transformer’s
high operating temperature. The filter produced the opposite result.

19. What does K-Rating really mean?
K-Factor
rating, applied to transformers, is an index of the transformer's ability to
supply harmonic content (%THDI) in its load current while operating
within its temperature limits. K-Rated transformers are only intended to survive
in a harmonic rich environment. They do not mitigate harmonic currents or
voltages. In fact, they normally cause higher levels of voltage distortion
because of their higher harmonic impedances.
20. Should I apply a transformer that
is only capable of supporting a sub-system with less than 50% nonlinear
electronic loads?
No! Most power
panels in a modern commercial facility support more than 95% nonlinear
electronic loads. On this basis, current distortion will probably approach or
even exceed 100% THDI.
A transformer
that is only designed to support a mix of 50% nonlinear loads and 50% linear
loads will, under full nonlinear load conditions, exceed its design losses and
temperature rise if loaded to much more than 75% of its nameplate rating. To
meet the 80% NEC requirement, this transformer, under these conditions, should
not be loaded to more than 60% of its nameplate rating.
We doubt that a
professional engineer would want to take the risk in applying this type of
transformer since, at least in the longer term, he has no control of the type of
loads that will be connected to the system. Because the load mix is becoming
more nonlinear, the risk increases over time.
Essentially the
same logic applies to retro applications. There is no guarantee that the
transformer might not eventually become overloaded.
This potential
problem is not merely a reliability issue. The higher losses will reduce the
transformer’s efficiency, and increase air conditioning and power costs.
21. Does the Department of Energy’s
Oak Ridge National Laboratory validate and endorse the performance of harmonic
mitigating transformers.
The Department
of Energy’s Oak Ridge National Laboratory does not evaluate or endorse the
performance of any manufacturer’s transformers because: (i) they lack the
statutory authority to do so and (ii) there are no established guidelines or
standards.
22. Are manufacturers’ published
transformer efficiency claims, under nonlinear load conditions, legitimate?
A number of
manufacturers now claim transformer efficiencies that meet or exceed the
requirements of NEMA TP 1-2002, under severe nonlinear load conditions.
One manufacturer has even published their test methods. At best, these claims
are misleading since:
a) There is no
recognized standard guide for determining the energy efficiency of distribution
transformers or a standard test method for measuring their energy consumption,
b) The
manufacturers that make these efficiency claims are basing them on the ‘Power In
– Power Out’ Measurement Method. Based on the manufacturer’s published test
method, which utilizes +/-0.3% revenue class instrumentation accuracy, the
measurement error will be +/-1.5%, when measuring the efficiency of a
transformer. As a result, a claimed efficiency of 98%, for a 75kVA transformer,
may, in fact, be only 96.5%. There are a number of IEEE transactions that
confirm that this test method will yield inaccurate results.
23. Why should I specify PQI
transformers?
As an
alternative to conventional, K-Rated or other harmonic mitigating transformers,
e-Rated®
Distribution TransFilters™ have the highest
confirmable efficiencies in the industry [1]. These efficiencies are probably 2%
better than any other harmonic mitigation transformers and typically between
6.5% and 15% better than conventional or K-Rated transformers, under typical
nonlinear load conditions.
[1]
Please refer to Transformer Efficiency and e-Rated Technology on this web site.
More
importantly, specifying engineers may also take advantage of PQI’s no-cost
engineered system solutions.
The PQI Solution™,
which has been refined by over thirty years of harmonic mitigating experience,
includes:
• A Statement
of Design Objectives,
• A comprehensive System Study,
• A detailed Mitigation Proposal and
• A system Performance Guaranteed.
The PQI Solution™
will often double or triple the power cost benefits provided by the replacement
of transformers alone.

e-Rated™ is a registered trademark of the
e-Rated
Transformer Corporation
|